Model GNT-385 with engine Torque TDE6L316TAD provides 350 kVA / 316 kW in Prime (PRP) mode and 385 kVA / 287 kW in Standby (ESP) mode. This is a practical industrial power unit for facilities with a stable operating load.
| Parameter | Value |
|---|---|
| Generator Model | GNT-385 |
| Engine Brand | Torque |
| Engine Model | TDE6L316TAD |
| Prime Power kVA | 350 kVA |
| Prime Power kW | 316 kW |
| Standby Power kVA | 385 kVA |
| Standby Power kW | 287 kW |
| Parameter | Value |
|---|---|
| Weight | 2900 kg |
| Height | 1800 mm |
| Weight | 1200 mm |
| Length | 2700 mm |
| Fuel Tank | 320 liters |
| Parameter | Value |
|---|---|
| Weight | 2900 kg |
| Height | 1800 mm |
| Width | 1200 mm |
| Length | 2700 mm |
| Fuel Tank | 320 liters |
| Parameter | Value |
|---|---|
| Engine Brand | TORQUE DIESEL ENGINE |
| Engine Model | TDE6L316TAD |
| Maximum Engine Power (Standby) | 316 kW |
| Maximum Engine Power (Prime) | 287 kW |
| Engine Volume | 12.88 liters |
| Engine RPM | 1500 rpm |
| Cylinders and Firing Order | 6 |
| Bore x Stroke | 135x150 |
| Governor Type | Elektronik |
| Electrical System | 24 V |
| Oil Volume | 40 liters |
| Coolant Capacity | 65 liters |
| Fuel Capacity | 320 liters |
| Fuel Consumption 100% | 64 l/hours |
| Parameter | Value |
|---|---|
| Standby Power | 385 kVa |
| Prime Power | 350 kVa |
| Voltage | 230/400 v |
| Voltage Tolerance | ±1 |
| Frequency | 50 Hz |
| Revolt | 1500 |
| Short Circuit Current | 0.0000 % |
| Insulation | H / IP23 |
| Alternator Capacity | 90 % |
Diesel generator GNT-385 based on the Torque TDE6L316TAD engine is suitable for facilities where not just a backup power source is required, but reliable coverage of heavy operating loads. This format is especially relevant for production sites, agricultural enterprises, processing facilities, warehouses, engineering bases, and commercial sites, where power outages directly affect process stability.
Power of 350 kVA / 316 kW in Prime (PRP) mode and 385 kVA / 287 kW in Standby (ESP) mode makes it possible to maintain the operation of process equipment, pump groups, ventilation, cooling, automation, lighting, and other critical systems at the facility. This is a solution for sites where a stable power supply is important not only in emergency mode, but also as part of the overall operational logic of the enterprise.
By its class, GNT-385 belongs to the range where the generator already becomes a serious industrial solution for operation under load. Such a unit is suitable for customers who need a working level of power, a clear power base, and a reasonable entry budget without moving into the more expensive upper segments.
GNT-385 is based on a 6-cylinder Torque TDE6L316TAD engine with a displacement of 12,88 liters, operating at 1500 rpm. This configuration is designed for extended duty cycles and makes the unit suitable for facilities where predictable powertrain performance and straightforward maintenance are important.
The engine delivers 287 kW in Prime (PRP) mode and 316 kW in Standby (ESP) mode, ensuring reliable coverage of the operational needs of industrial and agricultural facilities. At full load, fuel consumption is 64 l/h, and the built-in fuel tank with a capacity of 320 liters allows for planned autonomous operation without frequent refueling.
Generator GNT-385 is a pragmatic solution for facilities where the key selection criteria are operational reliability and a reasonable project cost. The dimensions of the enclosed unit — 2700 × 1200 × 1800 mm with a weight of 2900 kg — make it possible to integrate the generator into the site without special infrastructure solutions.